Ethernet Remote I/O Module M120

Ethernet Remote I/O Module M120

SGD 336

  • Rated Voltage: 12 ~ 36VDC;
  • 4DIN+4AIN+2AO+4DO+1RJ45+1RS485;
  • 1 RS485 Serial port, supports Modbus RTU Master or slave, can extend I/O modules;
  • Wet Contact (NPN or PNP), Dry Contact;
  • DO Sink or Pulse Output

The M120T Ethernet Remote I/O Module is an industrial class, isolated designed, high reliability, high stability and high precision data acquisition module, embedded 32-Bit High Performance Microprocessor MCU, Integrated 1 Industrial 10/100M adaptive Ethernet module inside. It provides multi I/O, supports standard Modbus TCP, can be intergraded into SCADA, OPC server, and other automation systems. It is design for working in the harsh industrial application environment, widely used in a variety of industrial automation, security monitoring system, automatically measurement and control system.

The M120T Ethernet Remote I/O module provides a RS485 interface, through the RS485 bus, it can cascade Modbus RTU I/O devices or Modbus RTU meters, e.g.: a variety of digital input or digital outputs, analog inputs or outputs, thermal resistance IO module combination, save costs. At the same time, the Ethernet Remote I/O module has register mapping function, the cascade Modbus RTU I/O data are automatically collected to the mapping memory area, the Modbus TCP Client query without waiting then can get a quick response to meet the industrial timely requirements.

The M120T Ethernet Remote I/O module provides 4 optical-isolated digital inputs, supports max. 700KHz high speed pulse counter, 4 isolated 12bits analog inputs, supports 0~5V,0~10V,4~20mA,0~20mA analog signal, 4 digital outputs, supports 10Hz~300KHz high speed pulse output or relay outputs, 2 channel 12bits analog outputs, supports 0~10VDC signal output. All of the I/O with high sampling frequency and special filtering strategy to ensure it’s reliable.

Specifications:

Ethernet Remote I/O Module Specifications

• Digital Input

Sensor Type

Wet Contact (NPN or PNP), Dry Contact

I/O Mode

DI or Event Counter

Dry Contact

• On: short to GND=1 • Off: open=0

Wet Contact (DI to COM)

• On: 10 to 30 VDC =1 • Off: 0 to 3 VDC=0

Counter Frequency

700KHz(Only the 1st Channel can be used as high speed pulse counter)

Digital sampling frequency

500Hz

Digital filtering strategy

Continues 3 times

Isolation

Optical Isolated,3k VDC or 2k Vrms

• Digital Output

Type

Sink

I/O Mode

DO or Pulse Output

Pulse Output Frequency

10Hz~300KHz(Only the 1st Channel can be used as high speed pulse outputs)

Over-Voltage Protection

50 VDC

Over-Temperature Shutdown

175°C (typical), 150°C (min.)

Load Current

Max. 500 mA per channel

Digital sampling frequency

500Hz

• Analog Input

Type

Differential input

Resolution

12 bits

I/O Mode

Voltage / Current (jumper selectable)

Input Range

0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA

Accuracy

±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C

Sampling frequency

20Hz

Isolation

Electrical isolation

• Analog Output

Type

Differential input

Resolution

12 bits

Output Range

0 to 10 VDC

Drive Current

1A (max.)

Accuracy

±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C

Isolation

No

• Working Power Requirements

Input Voltage

24 to 36 VDC, Peak Voltage:+40VDC, Power consumption: Less than 3W;

Input Current

139 mA @ 24 VDC

• Power Output

Output Voltage

24 to 36 VDC

Output Current

139 mA @ 24 VDC

• LAN

Ethernet

10/100 Mbps RJ45 ports

Protection

15KV ESD Protection

Protocols

Modbus TCP, TCP/IP,MQTT, TCP Server, TCP Client

Max. TCP Connection

5

• Serial Port

RS485

MODBUS- RTU Protocol, Modbus-ASCII Protocol

Protection

15KV ESD Protection

Modbus Slave address

1~255

Baud Rate

1200,2400,4800,9600,19200,38400,57600,115200,128000Bps;

Mapping registers

Bit Type: 300 Registers, 16-Bit Type: 300 Registers.

• Physical Characteristics

Wiring

I/O cable max. 14 AWG

Dimensions

105 x 88 x 30 mm

Weight

Under 205 g

Mounting

DIN rail or wall

• Environmental Limits

Operating Temperature

Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

5 to 95% (non-condensing)

Altitude

Up to 3000 m

 

Features:

1. Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog;

2. Wide range power supply 24 ~ 36VDC with over voltage and phase-reversal protection;

3. Management and configuration via LAN connection configuration software for easy operation and maintenance, Integrated 10/100M adaptive Ethernet module, supports Modbus TCP,MQTT protocol;

4. 4 optical isolated digital input, supports max. 700KHz high speed pulse counter;

5. 4 digital output or relay output, supports 10Hz~300KHz high speed pulse output;

6. 4 isolated analog input, 12-bit resolution, supports 0~20mA,4~20mA,0-5VDC, 0-10VDC;

7. 2 analog output, 12-bit resolution, supports 0-10VDC;

8.High sampling frequency and special filtering strategy to ensure reliability;

9. 1 RS485 Serial port, supports Modbus RTU/ASCII Master, can extend I/O modules;

10. Supports register mapping function and extend I/O inquiry strategy;

11. Provides 1 channel 24~36VDC power source output for external device, saving wiring cost;

12. LED instructions work status, with reset button to reset, easy on-site installation and  commissioning;

13. Using metal shell, protection class IP30. Metal shell and system security isolation,  especially suitable for industrial applications in the field;

14. Small size, L105 * W88 * H30mm, compatible wall installation and DIN35mm industrial rail installation.