Ethernet Remote I/O Module M150
Ethernet Remote I/O Module M150
SGD 336
- Rated Voltage: 12 ~ 36VDC;
- 8DIN+4AIN+4DO+1RJ45+1RS485;
- 1 RS485 Serial port, supports Modbus RTU Master or slave, can extend I/O modules;
- Wet Contact (NPN or PNP), Dry Contact;
- DO Sink or Pulse Output
The M150T Ethernet Remote I/O module provides a RS485 interface, through the RS485 bus, it can cascade Modbus RTU I/O devices or Modbus RTU meters, e.g.: a variety of digital input or digital outputs, analog inputs or outputs, thermal resistance IO module combination, save costs. At the same time, the Ethernet Remote I/O module has register mapping function, the cascade Modbus RTU I/O data are automatically collected to the mapping memory area, the Modbus TCP Client query without waiting then can get a quick response to meet the industrial timely requirements.
The M150T Ethernet Remote I/O module provides 8 optical-isolated digital inputs, supports max. 700Khz high speed pulse counter, 4 isolated 12bits analog inputs, supports 0~5V,0~10V,4~20mA,0~20mA analog signal, 4 digital outputs, supports 10Hz~300Khz high speed pulse output or relay outputs. All of the I/O with high sampling frequency and special filtering strategy to ensure it’s reliable.
The M150T Ethernet Remote I/O module can work at 12~36VDC with anti-reverse protection design. Also, it provides 1channel 12~36VDC power output for external device to save wiring cost.
Specifications:
Ethernet Remote I/O Module Specifications |
|
• Digital Input |
|
Sensor Type |
Wet Contact (NPN or PNP), Dry Contact |
I/O Mode |
DI or Event Counter |
Dry Contact |
• On: short to GND=1 • Off: open=0 |
Wet Contact (DI to COM) |
• On: 10 to 30 VDC=1 • Off: 0 to 3 VDC=0 |
Counter Frequency |
Max. 700kHz(Only the 1st Channel can be used as high speed pulse counter) |
Digital sampling frequency |
500Hz |
Digital filtering strategy |
Continues 3 times |
Isolation |
Optical Isolated,3k VDC or 2k Vrms |
• Digital Output |
|
Type |
Sink |
I/O Mode |
DO or Pulse Output |
Pulse Output Frequency |
10Hz~300KHz(Only the 1st Channel can be used as high speed pulse outputs) |
Over-Voltage Protection |
50 VDC |
Over-Temperature Shutdown |
175°C (typical), 150°C (min.) |
Load Current |
Max. 500 mA per channel |
Digital sampling frequency |
500Hz |
Isolation |
If DO is Sink type, then no isolation. If it is Relay, then is electrical isolation. |
• Analog Input |
|
Type |
Differential input |
Resolution |
12 bits |
I/O Mode |
Voltage / Current (jumper selectable) |
Input Range |
0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA |
Accuracy |
±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C |
Sampling frequency |
20Hz |
Built-in Resistor for Current Input |
162 ohms |
Isolation |
Electrical isolation |
• Working Power Requirements |
|
Input Voltage |
12~36VDC, Peak Voltage:+40VDC, Power consumption: Less than 3W; |
Input Current |
139 mA @ 24 VDC |
• Power Output |
|
Output Voltage |
12~36VDC |
Output Current |
139 mA @ 24 VDC |
• LAN |
|
Ethernet |
10/100 Mbps, RJ45 ports |
Protection |
15KV ESD Protection |
Protocols |
Modbus TCP, TCP/IP,MQTT,TCP Server,TCP Client |
Max. TCP Connection |
5 |
• Serial Port |
|
RS485 |
MODBUS- RTU Protocol |
Protection |
15KV ESD Protection |
Modbus Slave address |
1~255 |
Baud Rate |
1200,2400,4800,9600,19200,38400,57600,115200,128000Bps; |
Mapping registers |
Bit Type: 300 Registers, 16-Bit Type: 300 Registers. |
• Physical Characteristics |
|
Wiring |
I/O cable max. 14 AWG |
Dimensions |
105 x 88 x 30 mm |
Weight |
Under 205 g |
Mounting |
DIN rail or wall |
• Environmental Limits |
|
Operating Temperature |
Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature |
-40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity |
5 to 95% (non-condensing) |
Altitude |
Up to 3000 m |
Features:
1. Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog;
2. Power supply 12~36VDC with over voltage and phase-reversal protection;
3. Management and configuration via LAN connection configuration software for easy operation and maintenance;
4. Support Web real-time monitoring and Web debugging;
5. DO1 support PWM output;
6. Integrated 10/100M adaptive Ethernet module, supports Modbus TCP protocol;
7. 8 optical isolated digital input, supports max. 700Khz high speed pulse counter;
8. 4 digital output or relay output, supports 10Hz~300KHz high speed pulse output;
9. 4 isolated analog input, 12-bit resolution, supports 0~20mA,4~20mA,0-5VDC, 0-10VDC;
10. High sampling frequency and special filtering strategy to ensure reliability;
11. 1 RS485 Serial port, supports Modbus RTU Master or Slave, can extend I/O modules;
12. Supports register mapping function and extend I/O inquiry strategy;
13. Provides 1 channel 12~36VDC power source output for external device, saving wiring cost;
14. LED instructions work status, with reset button to reset, easy on-site installation and commissioning;
15. Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial applications in the field;
16. Small size, L105 * W88 * H30mm, compatible wall installation and DIN35mm industrial rail installation.
Additional information
Model | T-version, E-version |
---|
Reviews
There are no reviews yet.